UL Warns of Counterfeit Fire Sprinklers (Release No. 14PN-9)
NORTHBROOK, Ill., May 15, 2014 /CNW/ - The following is a notification from UL that the Fire Sprinklers identified below bear counterfeit UL Certification Marks for the United States and Canada. The Fire Sprinklers have not been evaluated by UL to the appropriate Standards for Safety and it is unknown if the Fire Sprinklers comply with any safety requirements.
Although the fire sprinklers wrench boss is marked "TYCO" and the thermo bulbs are marked "JOB F5" the fire sprinklers were not manufactured or labeled by Tyco and the thermo bulbs were not manufactured or labeled by Job, GmbH., affiliates or agents.
Name of Product: |
Upright TY3151 |
Pendent TY3251 |
|
Horizontal Sidewall PS007 |
Location: The sprinklers have been found in Vietnam and India. UL has not received reports of these counterfeit sprinklers in other locations.
Identification: On the product: The product bears counterfeit UL and TYCO Marks and the following information on the upright TY3151 sprinkler. (Location – Vietnam)
Counterfeit Fire Sprinkler Markings |
Authentic Fire Sprinkler Markings |
UL in a circle, 155° (degrees) F/68° (degrees) C, TY3151 |
cULus in a circle, 155° (degrees) F/68° (degrees) C,SU, TY3151 |
"TYCO" cast into both sides of the wrench boss |
"TYCO" incised on one side and the year of manufacture on the opposite side of wrench boss |
Deflector material zinc plated steel (magnetic) |
Defector material brass with chrome or painted white (non-magnetic) |
5mm glass bulb –Job F5 |
5 mm Geissler glass bulb – "G" between two triangles on one side and lot number on the other side |
Photographs of the product and packaging can be viewed at www.ul.com/newsroom.
Identification: On the product: The product bears counterfeit UL and TYCO Marks and the following information on the pendent TY3251 sprinkler. (Location – India)
Counterfeit Fire Sprinkler Markings |
Authentic Fire Sprinkler Markings |
cULus in a circle on the side of the frame. 68C, SSP, on the deflector |
cULus in a circle, 155° (degrees) F/68° (degrees) C,SP, TY3251 on the deflector |
"TYCO" cast into both sides of the wrench boss |
"TYCO" incised on one side of wrench boss |
Deflector material zinc plated steel (magnetic) |
Defector material brass with chrome or painted white (non-magnetic) |
5mm glass bulb –Job F5 |
5 mm Geissler glass bulb – "G" between two triangles on one side and lot number on the other side |
Photographs of the product and packaging can be viewed at www.ul.com/newsroom.
Identification: On the product: The product bears counterfeit UL and TYCO Marks and the following information on the pendent TY3251 sprinkler. (Location – Vietnam)
Counterfeit Fire Sprinkler Markings |
Authentic Fire Sprinkler Markings |
UL in a circle, 155° (degrees) F/68° (degrees) C, TY3251 |
cULus in a circle, 155° (degrees) F/68° (degrees) C,SP, TY3251 |
"TYCO" cast into both sides of the wrench boss |
"TYCO" incised on one side of wrench boss |
Deflector material zinc plated steel (magnetic) |
Defector material brass with chrome or painted white (non-magnetic) |
5mm glass bulb –Job F5 |
5 mm glass Geissler bulb – "G" between two triangles on one side and lot number on the other side |
Photographs of the product and packaging can be viewed at www.ul.com/newsroom.
Identification: On the product: The product bears counterfeit UL and TYCO Marks and the following information on the horizontal sidewall PS007 sprinkler. (Location – Vietnam)
Counterfeit Fire Sprinkler Markings |
Authentic Fire Sprinkler Markings |
UL and cUL in a circle, 55° (degrees) F/68° (degrees) C, without flow direction arrow, PS007 |
cULus in a circle, 155° (degrees) F/68° (degrees) C, Sidewall, R, TOP, WH, Q-71, HSW, SIDEWALL, FLOW, flow direction arrow, TY3331 |
"TYCO" cast into both sides of the wrench boss |
"TYCO" incised on one side and the year of manufacture on the opposite side of wrench boss |
Deflector material zinc plated steel (magnetic) |
Defector material brass with chrome or painted white (non-magnetic) |
5mm glass bulb –Job F5 |
5 mm Geissler glass bulb – "G" between two triangles on one side and lot number on the other side |
Photographs of the product and packaging can be viewed at www.ul.com/newsroom.
About UL
UL is a premier global independent safety science company that has championed progress for 120 years. Its more than 10,000 professionals are guided by the UL mission to promote safe working and living environments for all people. UL uses research and standards to continually advance and meet ever-evolving safety needs. We partner with businesses, manufacturers, trade associations and international regulatory authorities to bring solutions to a more complex global supply chain. For more information about our certification, testing, inspection, advisory and education services, visit http://www.UL.com.
Michelle Press
Marketing Manager
UL
T: 1 847-664-1966
E: [email protected]
Release No. 14PN-9
SOURCE: UL
http://www.ul.com
Share this article